Gas detection control unit for measurement of flammable and/or toxic gases as well as oxygen. Smoke detectors as option. Graphic display. Menu guided configuration. 3 Alarm levels per channel. 12 freely configurable relays. Analog outputs 4…20 mA (only ET-4DA2).
Features
Number of Transmitters:
Signal Processing:
-
Microcontroller with A/D-Converter
Alarm/Fault/Indication:
-
Illuminated graphic display (160 x 80) for indication of measured values, messages and alarms
-
12 (3 x 4) red LEDs for alarm indication
-
LEDs for indication of channel fault (4 x yellow), channel operation (4 x green), operation (1 x green), device fault (1 x yellow)
User Interface:
-
Menu guided system via graphic display and keys
-
Completely configurable at device, no tools needed
-
3 password protected servicing levels
Alarm Evaluation:
-
3 freely adjustable alarm levels per channel
-
Monitoring: over-scale, under-scale or min/max
-
Latching of each alarm configurable
Relays, potential free:
-
12 change-over contacts 230 V / 5 A (total power consumption: max. 10 A), freely configurable with Alarm 1 to 3 and transmitter fault
-
2 change-over contacts 230 V / 5 A for maintenance mode and device fault
Additional Features:
-
Adjustment of zero point and sensitivity of measuring channels
-
RS 232/RS 485-Interface for communication with external periphery (PC or PLT-System)
-
Key switch function (maintenance mode)
-
Horn reset
-
Alarm reactivation
-
4 Digital inputs, potential free
-
4 Analog outputs 4-20 mA/0-10 V, potential free (only ET-4DA2)
Operation Temperature:
-
-10 °C to +40 °C, Humidity: non condensing
Storage Temperature:
-
-25 °C to +60 °C, Humidity: non condensing
Options
-
ProfiBus, ModBus, Ethernet connection, Visualisation ET-View, …(with integrated ProfiBus DP-Module: ET-4DP2, 24 V (Art. 315010))
Types
-
230VAC or 24VDC
-
Wall mounted housing
-
DIN rail
-
Control panel
-
19” Rack
All control units of the ET-Series could be used in combination with all ExTox Transmitters ExSens(-I) and Sens(-I)
Our control units in combination with the ExTox Transmitters comply with the requirements of EN 60079-29-1, EN 45544-1 to EN 45544-3 and EN 50104 for Gas Detection Systems. Furthermore are those in conformity to the European Directives 2014/34/EU (ATEX), 2014/30/EU (EMV), 2014/35/EU (LVD).
Support
Here you can download detailed information about our products, applications and systems