Software package for Personal Computers consisting of
ET-View - Online-Visualisation for in maximum 16 Gas Warning Control Units; Data logging on PC-harddisc
ET-Diag - History diagrams of logged data
Features:
Visualisation:
-
Individual text to identify each measuring point (channel)
-
Indications for operation, alarms, transmitter fault
-
Measuring values with physical unit and gas
-
Indications for ET-8D-status operation, maintenance, fault and data transmission
-
Cycle time for actualization configurable
-
Visualisation of all connected control units simultaneously
Data logging:
-
Capacity depends on hard disc only
-
Recorded data includes time stamp and all of the visualized data
Data loop through:
-
Data transmission to external periphery, e. g. PLC, possible
Diagram:
-
x-y-diagrams (up to two y-axis, scalable)
-
Basic time intervals: day or month
-
Zoom functions
-
Options: Copy, save and print of the displayed diagram
Control units:
-
Up to 16 control units ET-8D or ET-4D2
System requirements:
Personal Computer (Operating System):
-
Microsoft Windows 2000/XP/Vista™/Windows 7
Communication (Control Unit <-> PC):
-
RS 485 interface (or RS 485-adapter for RS232- or USB-ports)
Control units:
-
Suitable software version (ask ExTox for information)
-
Configuration of RS 485-address on PCB of the control unit (see operating manual)
Transmission parameters:
-
9600 Baud, 8 Data bits, 1 Stop bit, no parity
Cabling:
|
Downloads